経年ガス絶縁機器の現地耐電圧試験による更新時期の検討
—課電履歴を考慮した絶縁故障確率の評価—
五島 久司八島 政史新藤 孝敏宅間 董
著者情報
ジャーナル フリー

2009 年 129 巻 9 号 p. 1123-1130

詳細
抄録

Many of the electric power apparatuses that were installed at the period of high economic growth in Japan are reaching their supposed lifetime. Therefore, an important issue is how to effectively maintain, manage, and replace the many aged electric power apparatuses. Hence, it is necessary to develop a condition diagnosis technique and a method of confirming the healthy condition of an aged power apparatus. Consequently, the establishment of a maintenance standard for such aged power apparatuses, which is helpful for judging the possibility of prolonged operation with satisfactory reliability and the replacement time, is required.
From the above-stated viewpoint, we have aimed to establish a method of judging the condition of aged power apparatuses by executing on-site insulation tests. If an insulation test of the aged power apparatus is executed, it is important to estimate the risk (increase in the cumulative insulation fault probability) considering the background (life-stress) of the voltage application, including the on-site insulation test. In this paper, we discuss the influence of the insulation test of aged power apparatus on the cumulative insulation fault probability using a Weibull distribution.

著者関連情報
© 電気学会 2009